Sign In | Join Free | My futurenowinc.com |
|
Brand Name : ZGD
Model Number : ZGD33-80K (L)
Place of Origin : Guangdong, China
MOQ : 1
Price : $400.00/Pieces 1-9 Pieces
Payment Terms : Western Union, L/C, T/T
Supply Ability : 10000 Piece/Pieces per Month
Delivery Time : 15-30 work days
Phase : Three Phase
Protection : Lightning
Weight : 113kg
Type : On-line
Application : COMPUTER
Product name : Online UPS Systems
Capacity : 80KVA
Wave Form : Pure Sine Wave
Battery Type : Lead Acid Battery
Color : Black
Certificate : CE,ULRohs,GS
Input voltage : 305-478VAC
Display : LCD
Name : High Frequency Ups Power
Products : Three Phase Online UPS
Port : Shenzhen
1. Product Introduction
Wide range of input voltage can suitable for bad power condition area.
Special design and provide high reliability, high ratio Uninterruptible Power Supply for personal computer and enterprise key terminal.
Automatic Power ON, unattended function.
2. Product Features
Generator can conntected
Wide range of input volatge from 135V to 280V, can suitable for bad power condition area
Automatic voltage regulating function, stablilze output voltage, ensure security and stability of electrical equipment.
Perfect battery management technology, automatic adjust the termination voltage and extend battery life
Support cold start function, start UPS without electric supply, meet emergency demand.
Model | GH33 | ||||
60KL | 80KL | 100KL | 120KL | ||
PHASE | |||||
CAPACITY | 60KVA/54KW | 80KVA/72KW | 100KVA/90KW | 120KVA/108KW | |
INPUT | |||||
Nominal Voltage | 3 x 400 VAC (3 Ph+N) | ||||
Voltage Range | 190-520 VAC (3-Phase) @ 50% Load; | 208-478 VAC (3-Phase) @ 70% Load; | |||
305-478 VAC (3-Phase) @ 100% Load | 305-478 VAC (3-Phase) @ 100% Load | ||||
Frequency Range | 46~54 Hz or 56~64 Hz | 40~70 Hz | |||
Power Factor | ≥0.99 @ 100% Load | ||||
OUTPUT | |||||
Output Voltage | 3 x 360*/380/400/415 VAC (3 Ph+N) | 3 x 380/400/415 VAC (3 Ph+N) | |||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||
Frequency Range (Synchronized Range) | 46~54 Hz or 56~64 Hz | ||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||
Current Crest Ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≤2 % THD (Linear Load); | ≤2 % THD (Linear Load); | |||
≤4 % THD (Non-linear Load) | ≤4 % THD (Non-linear Load) | ||||
Transfer Time | AC Mode to Batt. Mode | Zero | |||
Inverter to Bypass | Zero | ||||
Waveform (Batt. Mode) | Pure Sinewave | ||||
Overload | AC Mode | 100-110% for 10 min, 110-130% for 1 min, | 105-110% for 1 hr, 111-125% for 10 min, | ||
>130% for 1 second | 126-150% for 1 min, >150% for 200 ms | ||||
Battery Mode | 100-110% for 30 seconds, 110-130% for 10 seconds, | 105-110% for 1 hr, 111-125% for 10 min, | |||
>130% for 1 second | 126-150% for 1 min, >150% for 200 ms | ||||
Parallel Capacity | up to 3 units in parellel | up to 2 units in parellel | |||
EFFICIENCY | |||||
AC Mode | 94.00% | 94.50% | |||
ECO Mode | 97.00% | 98.00% | |||
Battery Mode | 93.50% | 94.50% | |||
BATTERY | |||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | |||
Numbers | 32~40 pcs (Adjustable) | ||||
Charging Current (Max.) | 8A | 24A | 32A | ||
Charging Voltage | +/- 13.65V x N (N=16~20) | +/- 13.7V x N (N=16~20) | |||
INDICATORS | |||||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | 5.7" monochrome LCD or 10" Touch Type color LCD | |||
ALARM | |||||
Battery Mode | Sounding every 2 seconds | ||||
Low Battery | Sounding every 0.5 second | ||||
Overload | Sounding every second | ||||
Fault | Continuously sounding | ||||
PHYSICAL | |||||
Long-run Model | Dimension | 790*360*1010mm | 940*567*1000mm | ||
Net Weight (kgs) | 108 | 113 | 194 | 229 |
![]() |
72KW 80KVA UPS Power System Three Phase Long Runtime Ups Images |